| Capacity | 128 to 1024 points |
| Test Levels | Low Voltage Test: less than or = 5 volts 6mA max current Insulation Resistance & Dielectric (Hipot) Test: 1000: OFF, 50-1000 VDC ±5% (optional 50-700 VAC ±5%) 1500: OFF, 50-1500 VDC ±5% (optional 50-1000 VAC ±5%) |
| Sensitivity | Connection Resistance: .1 to 100K ohms ± 1% ± .1 ohm, also 500K, 1M, and 5M ohms ±10% 4-wire: .001 to 10 ohm ±2% ± .001 ohm High Voltage Insulation Resistance: 5M, 10M, 20M, 50M, 100M, 200M, 500M, 1000M ohms ±10% Capacitance: 5nF to 100µF ±10% ± .02nF (10% tolerance) |
| Component Tests | Diodes: Silicon, LEDs, Zeners with negative bias breakdown <4V Resistors: .1 Ohm to 100K Ohm, ± 1% (default tolerance 10%) Capacitors: 5nF to 100uF, ± 10%, ± .02nF (Learn Range is 400nF to 100uF) |
| Test Rate | Connection Test: 128 points / .25 second (typical) Hipot Dwell: 10 ms to 120 Sec. duration per net High Speed Hipot: user selectable, On / Off |
| Max Capacitance Per Net for Hipot Test | 0.2µF @ 300VDC, 80nF @ 500VDC, 20nF @ 1000VDC |
| Max Points Per Net | 100 |
| HV Energy Limit | 35 mJoules |
| Usable Humidity Range | 0 to 95% RH (WARNING, I.R. and DWV test results will degrade when Relative Humidity exceeds 75%) |
| Printer Output | Standard Centronics type parallel interface. |
| Serial Port | RS-232 interface. Uses DB9 female connector. |
| Probe | Accessory for test point identification. |
| Memory | Nonvolatile storage of up to 99 wirelists. |
| Power | 100-255VAC, 50-60 Hz., MAX 50W |
| Size | Main unit: 14.25" x 6.75" x 5.25" (36 x 17 x 13.5 cm) Add-on: 6.25" x 6.75" x 5.25" (16 x 13.5 x 13.5 cm) |
| Weight | Main unit: 9.7 lbs. (4.4 kg) Add-on: 6.3 lbs. (2.8 kg) |
| Display | 4 Line x 20 character LCD |
| Warranty | One (1) year parts and labor. Replacement modules available next working day. |