![]() |
Cable Testers and Harness Testers Made Easy! | |
Insulation Compression Failures |
![]() |
|
![]() Compression damage can cause insulation to fail, causing current leakage, arcing, and even dead shorts. ![]() This close up shows how even plastic tie wraps can cause compression damage on soft insulation.
Metal brackets, grommets, clamps, overly tight strain relief's, all can cause cable failures due to compression damage.
Bare wire, tightly wrapped around braided shielding and then soldered, caused DWV failures in this cable. |
Test Results:Failures indicated while testing the cable
Necessary Conditions:Pressure on insulation in a bundle of wires from anything like the following
Aggravating Conditions:Conditions that could contribute to, or worsen, the effects of this problem
Root Cause:Insulation that has narrowed from its normal thickness due to compression from physical features/components in the assembly or in the environment of the installed application.Understanding the Failure Mechanism:
Confirmation of Root Cause:One or more of the following might be used to verify the defect
General Recommendations:
|
Problem 1A cable assembly house experienced a jump in DWV failures in their cables. The cable contained a number of TFE insulated and shielded twisted pair wires. The shields were terminated as a group by exposing about .3" of the shield and wrapping a bare wire around the exposed shields and then soldering them. Previously these cables had been built with a separate shield termination for each wire. |
DiscoveryUsing the confirmation methods, they discovered that the wrapped bare wire was creating compression and the soldering was allowing the TFE insulation of the twisted pairs to short to the shields. |
SolutionAssemblers returned to using shield terminations that were designed to heat shrink and solder terminate. |
||||
Problem 2Another cable assembly house was building cables used in GPS systems in motor homes. A large percentage of the cables failed hipot testing but, since no visually apparent problem was found, and the customer didn't require hipot testing, it was dropped. In time assemblies were returned as defective. Testing with low voltage, most of these defectives still passed as good. |
DiscoveryWhen testing on a high voltage tester, the returned cables failed consistently with DVW failures. Using the "divide and conquer" method the problem was traced to pieces of braided shielding that were penetrating extremely soft insulation on wires that were tightly fastened with a cable tie. |
SolutionExtra insulation was added to the areas where the insulation breach compression failures were occurring. |
||||
© Cirris Systems Corp.